4.1.7 Water testing

 

It is important that responsibilities for routine and ad hoc water testing are well defined by the Water Safety Group.

Each NHS board should have processes in place for the receipt, reporting and distribution of results which should include as a minimum:

Water testing at commissioning

What to test

A sampling plan with appropriate microbiological parameters and should be agreed by WSG prior to tender. As a minimum it should include testing in all settings for:

Testing for P. aeruginosa should be carried out in high-risk settings.

Local risk assessment should determine if there are additional testing requirements.

When to test

Samples should be taken no sooner than five days and no later than seven days after a full disinfection process has been completed and a further set of samples should be taken immediately prior to handover.

Actions following commissioning results

As part of their commissioning water safety plan, the NHS board should have pre-agreed processes in place should the results of commissioning tests be unsatisfactory. For more details on commissioning, see SHTM 04-01 Part A and BS 8680.

Routine water testing

Results from routine water testing over time (trend analysis) provides evidence of effective control measures and also supports early detection of HAI risks.

What to test

The WSG should agree the routine water testing required and this should form part of the water safety plan. As a minimum:

Frequency of testing 

As a minimum, testing for P. aeruginosa and Legionella spp. in high-risk settings should occur every 6 months.

The frequency of routine microbiological water testing in other areas and for other microorganisms should be based on a comprehensive risk assessment undertaken by the WSG.

Increases to the frequency of water testing should occur:

Consideration should be given to increasing the frequency of routine water testing when pre-flush trend analysis demonstrates increasing colony forming units (cfu)/100 ml for P. aeruginosa.

Microbiological limits

Healthcare water systems

Recommended microbiological limits for water samples are detailed in the table below.

Note: Incubate drinking water system samples at 22˚C and 37˚C for 24 hours in accordance with BS EN ISO 6222.

Microbiological limits for healthcare water systems

Pathogen

Colony Forming Units (CFU)

Coliform bacteria (including Escherichia coli) 0 cfu/100ml
Enterococci 0 cfu/100ml
P. aeruginosa 0 cfu/100ml
Legionella spp. Undetectable in high-risk units.
<100 cfu/litre in non-high-risk units
Legionella pneumophila serogroup 1 (Lp1) Undetectable
For all other gram-negative healthcare water system-associated organisms 0 cfu/ml

 

Additional microbiological limits 

The table below details recommended additional microbiological limits for water samples obtained from water dependent equipment.

Recommended additional microbiological limits for healthcare procedures that present an increased risk

Procedure

Colony Forming Units (CFU)

Total Viable Count 

(TVC)

Endotoxin

Heater cooler unit water 0 cfu/100ml for Mycobacterium spp. TVC cut-off levels of <100 cfu/ml None
Hydrotherapy water <20 cfu/litre for Legionella spp.

0 cfu/100ml for Staphylococcus aureus as part of wider investigations only (local decision)
TVC cut-off levels of <10 cfu/ml None
Endoscopy final rinse water 0 cfu/100ml for Mycobacterium spp. TVC cut-off levels of <10 cfu/100 ml Endotoxin limit of <0.25 EU/ml
Final rinse water in surgical instrument washer disinfectors TVC cut-off levels of <1 cfu/100 ml None Endotoxin limit of <0.25 EU/ml
Renal dialysis fluid and water TVC cut-off levels of <50 cfu/ml None  Endotoxin limit of <0.125 EU/ml

 

 

Selection of outlets for sampling 

For routine testing, samples collected should be pre-flush only unless otherwise directed by the WSG/IPCT or Microbiology.

If post-flush samples are to be taken, the sample should be collected after first running the outlet to flush through the pipes. Post-flush samples may support differentiation between local and systemic colonisation following a positive pre-flush result (see BS 7592 for more information).

A planned targeted sampling plan should be developed by the WSG to include:

Take samples from the proximal and distal ends of each water system with a locally agreed number of sampling points between.

Interpretation of routine water testing results

Sampling results and actions following a non-compliant result (no patient cases)
Remedial actions following positive water results (no patient cases)

Remedial actions should be agreed by the WSG.

Remedial actions should be determined based on consideration of the water test results in context with the water system as a whole, any existing control measures, and the areas where the result has been obtained.

For more information on whole water system disinfection see  (SHTM 04-01 part D ‘Disinfection of Domestic Water Systems’